Article number:SK 3187.630
BenefitsAn average of 75% energy savings due to speed-regulated components and heat pipe technologySuitable for international use due to a unique multi-voltage capabilityLonger service life of the components inside the enclosure and the cooling unit due to component-friendly coolingIntuitive operation due to touch display and intelligent interfaces
MaterialStainless steel 1.4301 (AISI 304)
ColorRAL 9007
Supply includesNano-coated condenser
Integral electric condensate evaporation
Assembly components
Wired ready for connection (plug-in terminal strip)
OptionsFor remote monitoring and networking of cooling units and chillers, use the Blue e+ Generation IoT Interface, item number 3124.300. Increase machine availability and process safety by remote monitoring of device data, condition, and system messages.
Total cooling output to DIN EN 14511Cooling output L35 L35/50 Hz: 2.6 kW
Cooling output L35 L35/60 Hz: 2.6 kW
Cooling output L35 L50/50 Hz: 1.82 kW
Cooling output L35 L50/60 Hz: 1.82 kW
( Cooling output L35 L35/50 Hz: 8,872 BTU/h
Cooling output L35 L35/60 Hz: 8,872 BTU/h
Cooling output L35 L50/50 Hz: 6,210 BTU/h
Cooling output L35 L50/60 Hz: 6,210 BTU/h )
Rated operating voltage110 V - 240 V, 1~, 50 Hz/60 Hz380 V - 480 V, 3~, 50 Hz/60 Hz
Rated output1.05 kW
Air throughput (unimpeded air flow)External circuit: 1,250 m³/h
Internal circuit: 1,250 m³/h
( External circuit: 735.7 cfm
Internal circuit: 735.7 cfm )
Energy efficiency ratio (EER) 50/60 Hz L35 L35Refrigeration factor L35 L35 (EER) 50 Hz: 2.63
Refrigeration factor L35 L35 (EER) 60 Hz: 2.63
Seasonal energy efficiency ratio (SEER) 50/60 Hz6.2
Versionwall-mounted
DimensionsWidth: 450 mm
Height: 1,600 mm
Depth: 294 mm
( Width: 17.7 ˝
Height: 63 ˝
Depth: 11.6 ˝ )
Protection category IP to EN 60 529Internal circuit IP 55
Protection category NEMAUL Type 3R/12
Refrigerant/cooling mediumRefrigerant: R134a
Quantity: 1.15 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 1.64 t
( Refrigerant: R134a
Quantity: 2.5 lb. )
Temperature controle+ controller (factory setting +35 °C)
Operating temperature range-20 °C...60 °C
( -4 °F...140 °F )
Storage temperature range-40 °C...70 °C
( -40 °F...158 °F )
Setting range20 °C...50 °C
( 68 °F...122 °F )
Rated power PelPower consumption L35 L35/50 Hz: 0.99 kW
Power consumption L35 L35/60 Hz: 0.99 kW
Power consumption L35 L50/50 Hz: 0.94 kW
Power consumption L35 L50/60 Hz: 0.94 kW
Permissible operating pressure (p. max.)24 bar
( 348.1 PSI )
NotePlease observe the assembly instructions.Firmware can be updated using the RiDiag III software (3159.300)
Weight/packaging unit54.8 kg
( 120.8 lb. )
Packaging unit1 pc(s).
Customs tariff number84158200
EAN4028177934672
ETIM 7.0EC000855
ECLASS 8.027180704
Product descriptionSK cooling unit Blue e+, wall-mounted, 2.6 kW, 110-240 V, 1~, 380-480 V, 3~, 50-60 Hz, Stainless steel, WHD: 450 x 1600 x 294 mm